125kW Bidirectional PCS
Product Description
The YTPCS-PCS/125 is a dedicated bidirectional Power Conversion System developed by YT-Electric for high-efficiency energy storage integration in industrial and commercial environments. With its robust DC voltage range of 600V–1000V, and full-load operation from 630V–950V, it ensures compatibility with most high-voltage battery clusters.
Delivering 125kW of rated power on both AC and DC sides, this PCS supports seamless charge/discharge operations, with DC current up to 198A, and AC current rated at 180A. The unit is designed with three-phase four-wire AC access, and maintains excellent grid interaction performance with THDi ≤3%, power factor 0.99, and DC component ≤0.5%.
The system is engineered for both grid-connected and off-grid operations, with grid-disconnected AC output THDU ≤3% (linear load) and 100% unbalanced load support, making it highly adaptable in fluctuating load conditions. It also boasts conversion switching times under 100ms, ensuring uninterrupted energy flow during mode transitions.
With an efficiency of over 99%, and full-load efficiency >98%, the PCS maximizes return on investment while minimizing losses. The unit is compact (520×240×680mm) and lightweight (<70kg), allowing for easy installation even in space-constrained environments.
Rated for altitudes up to 3000m (with derating), ambient temperatures from -30°C to 60°C, and humidity up to 95%, the YTPCS-PCS/125 is ready for tough operating conditions. Forced air cooling and smart airflow design ensure thermal stability during prolonged operation.
This converter is ideal for battery energy storage systems in factories, EV charging stations, data centers, and renewable hybrid systems seeking stable, high-efficiency energy conversion with precise grid support.
Technical Specifications
Product Name |
125 kW PCS |
![]() |
||
Factory Model |
YTPCS-PCS/125 |
|||
DC Side Parameters | ||||
DC voltage range |
DC600V~1000V |
|||
limited load voltage: |
DC600V-630V,DC950V-100 |
|||
Full-load voltage range |
DC630V~950V |
|||
Rated DC current |
198A |
|||
Rated DC power |
125kW |
|||
AC Grid-connected Parameters | ||||
Rated AC power |
125kW |
|||
Overload capacity |
1.1 times |
|||
Ambient temperature |
≤ 40°C |
|||
Rated voltage |
AC400V |
|||
Rated AC current |
180A |
|||
AC access method |
Three-phase four-wire |
|||
Grid voltage range |
400V (-15%~+15%) |
|||
Grid frequency range |
50Hz/60Hz±2.5Hz |
|||
THDi |
≤ 3% (full load) |
|||
Power factor |
0.99/-1~1 |
|||
Current DC component |
≤0.5% |
|||
Charge and discharge conversion duration |
<100ms |
|||
AC Grid-disconnected Parameters | ||||
AC grid-disconnected voltage |
AC400V |
|||
AC voltage range |
AC400V±3% |
|||
AC grid-disconnected frequency |
50Hz/60Hz |
|||
Grid-disconnected output THDU |
≤ 3% (linear load) |
|||
Unbalanced load capacity |
100% |
|||
Other Parameters | ||||
Maximum conversion efficiency |
≥99% |
Full load maximum efficiency > 98% |
||
Allowable ambient temperature |
-30℃~60℃ |
≥50℃ derating |
||
Allowable relative humidity |
≤95% |
No condensation |
||
Noise |
≤75dB |
|||
Protection grade |
IP20 |
|||
Altitude |
3000 m |
≥2000m for limited load |
||
Dimension |
W520mm×H240mm×D680mm |
|||
Weight |
≤70KG |
|||
Altitude |
≤ 2000m Rated Capacity, >2000m (derating 1% per 100m) |
|||
Cooling method |
Forced air cooling |
|||
Wiring, air flow design |
Primary/secondary connection: front air inlet: front air outlet: rear |
|||
BMS communication interface |
CAN or 485 |
|||
EMS communication interface |
Ethernet or 485 |
|||