Smart Power Factor Correction

Products

Smart Power Factor Correction

Power electronics three-phase load imbalance automatic regulation device uses advanced power electronic technology and automatic control technology, different from the traditional capacitor,reactor passive scheme, the use of active scheme to comprehensively solve the power quality problems such as three-phase load imbalance, reactive power, harmonics, especially suitable for low-voltage distribution column transformer power quality comprehensive control field

    Product Description

    Power electronics three-phase load imbalance automatic regulation device uses advanced power electronic technology and automatic control technology, different from the traditional capacitor, reactor passive scheme, the use of active scheme to comprehensively solve the power quality problems such as three-phase load imbalance, reactive power, harmonics, especially suitable for low-voltage distribution column transformer power quality comprehensive control field

    SPC-Product-ImageYT-SPC-1000 series product diagram

    Ordering instruction

    SN Item Ordering instruction
    1. YT-LCD Human Machine Interface 1. The LCD HMI Human Machine Interface is a 7-inch touch LCD screen,  
    which  can  be  used  for  module  parameter  setting,  data viewing and other functions.
    2.     Communication Method 1. Device  standard  communication  configuration:  one  channel RS485,  
    one  channel  Bluetooth.  (Bluetooth  for  mobile  APP debugging)
    2. Optional module: GPRS.
    3. Mounting bracket 1. SPC has two modes of column installation and ground installation, both of which require corresponding installation brackets. The mounting bracket is not a standard accessory, and can be purchased separately when customers need it.
    4. Power cable 1. The connecting cable between the device and the transformer is not  a  
    standard  part,  and  is  purchased  separately  when  the customer needs it.
    5. Current transformer 1. External  sampling  current  transformer  is  not  standard   configuration,   and can be purchased separately when customers need it.
     2. Current  transformer  split/closed  type,  indoor/outdoor  type, open/closed type price difference is relatively large, need to pay attention to purchase.

    Parameters indicators

    Electrical parameter Voltage level The standard voltage is 400V
    Operating frequency 50Hz ±5Hz
    Electrical   connection Three-phase four-wire (standard)/three-phase three-wire (customizable)
    Functional parameter Compensation mode

    Three phase load imbalance compensation,reactive power compensation and harmonic compensation,you can set one or more compensation methods

    Three-phase unbalance compensation Active current imbalance ≤5%
    Reactive        power compensation effect Reactive power compensation rate ≥98%
    Filter range 2 ~ 50 harmonics (number can be selected)
    Filtering effect Harmonic filtering rate  ≥95%
    Response time < 5ms
    System           active power loss 3%
    Communication mode Standard configuration: 1 RS485,1 Bluetooth, Modubus protocol
    Structural characteristic Cooling mode Adjustable speed intelligent fan
    Class of protection IP42
    noise < 60dB
    Installation mode Pole mount or floor mount
    Ambient Temperature -20 ~ 55℃
     
    Environmental requirement temperature  
    Relative humidity Max 95%, no condensation
    Installation elevation ≤ 1500m,  greater  than  1500m,  appropriate capacity reduction
    Heat       dissipation mode   Forced air cooling
      Air in/air out mode Air in on the left side, air out on the right side

    Specifications and models

    Module parameters

    Type Capacity Voltage level Type of   connection Harmonic function Dimension   (W*H*D)mm Weight kg
    YT-SP-1000/30-4-4L-A1 30kvar 400V 3P4W Yes 770x955x390 60kg
    YT-SPC-1000/50-4-4L-A1 50kvar 400V 3P4W Yes 770x955x390 65kg
    YT-SPC-1000/75-4-4L-A1 75kvar 400V 3P4W Yes 770x955x390 90kg
    YT-SPC-1000/100-4-4L-A1 100kvar 400V 3P4W Yes 770x955x390 110kg
    Instructions:
    1)    Default configuration: no LCD screen, 1 RS485+ Bluetooth module.
    2)     -A0: no harmonic function.
    3)    External current transformers, power cables, and mounting brackets are not standard accessories and need to be ordered separately.

    Dimensions drawing

    1
    YT-SPC-1000 Device dimensions drawing

    Installation diagram

    1
    Single pole installation diagram
    2
    Floor installation diagram

    SPC parts selection table

    SPC parts selection table

        SPC Capacity Circuit breaker Rated current Power Cable(mm2) CT Twisted pair   Current transformer (External sampling CT)
    A/B/C Phase     N     PE   Installation distance     Cross area
    30kvar 80A 25 25 16     1) The CT primary current is selected
    50kvar 125A 35 35 16
    75kvar 160A 50 50 16 ≤20m
    ≥20m
    2.5mm2 4.0mm2 according to the rated capacity of the

    transformer (KVA) of

    2 to 2.5 times. 2) When selecting CT, attention must be paid to the installation of the internal diameter, external size and busbar size of the current transformer.
    100kvar 250A 70 70 35
    125kvar 250A 95 95 50
    150kvar 350A 120 120 70
    175kvar 400A 150 150 95
    200kvar 400A 185 185 95
    Instructions: 1. The cross-sectional area of the power cable is based on the carrying capacity of the YJV cable in the air.

    SPC typical design scheme

    1
    Field application diagram
    2
    Field primary electrical drawing

    Design description:

    1) The sample CT is generally installed on the load side (as shown above), and can also be installed on the power side (left side of the SPC access point).

    2) The SPC is a high-power device, and the ventilation on the inlet/outlet side must be smooth.

    Technical Parameter

    Rated Voltage 220V(155-259V)
    400V(296-465V)
    480V(346-516V)
    Rated Current 30-100kvar/15-150A       30-100kvar/15-150A          50-150A
    Main Frequency 50/60Hz±5%
    Circuit Topology Three-level
    Compensation Modes Harmonic/reactive power/three-phase load imbalance compensation
    Filter Range 2 to 51 odd harmonics (selective or fully compensated)
    Harmonic Reduction Rate Filtering range 2 to 25th harmonic,100%of rated capacity (selectively or fully)
    Filtering Performance ≥97%
    Target Power Factor Adjustable rangefrom -1.0 to +1.0
    Three-Phase Load Balancing ≤5%to mitigate negative and zero sequence currents
    Linear Filtering Capability 3 times rated filter current (in case of 4-wire equipment)
    Switching/Control Frequency 25.6kHz
    Initial Response Time ≤50us
    Total Response Time ≤5ms
    System Effective Loss ≤2.5%
    Output Current Control Automatically limited to 100%output of rated capacity
    Control Algorithm

    FFT,Adaptive Control Algorithm,Fast Fourier &Instant Reactive Power Algorithms

    Controller DSP+FPGA
    Protection Hardware protection,software protection
    Control Connections Electrical Connections
    Human Machine Interface 4.3-inch/7-inch/10-inch touchscreen TFT LCD HMI
    Noise <60db(<45db at low speed operation)
    Installation method Module embedded (rack),wall-mounted,floor-mounted
    Protection level IP42
    Cooling method Speed control intelligent air-cooled PWM fan
    Colour RAL 7035 Industrial Grey/Black
    Ambient Temperature -20~55℃
    Relative Humidity 95%max,no condensation
    Altitude Rated capacity at altitude ≤2000m,reduced capacity at altitude >2000m
    Certification CE,IEEE61000,Type Test Report,ISO9001:2015
    Standards Compliance IEEE 519,ERG5/4
      Communication Protocol Adopts Modbus RTU remotecommunication protocol and TCP/IP protocol;Two  channel RS485 and CAN bus,support mobile APP operation,support Ethernet