Simple Rules for Solving Power Quality Mysteries
ABSTRACT
The typical Power Quality Problem starts with a frantic call to the facility’s engineer or electric shop supervisor concerning some malfunction that has either shut down production or caused a computer-based system to reset. After the fact, forensic-type investigations are probably the most difficult way to track down the source of a problem related to the quality of power. Following several simple rules can allow persons charged with such responsibilities quickly to mitigate most of such problems. It requires only a basic knowledge of electricity and how the various parameters relate in the presence of changes caused by loads, utility-switching, and other sources of power quality phenomena. It also requires a power quality monitor capable of reliably capturing the necessary information.
BACKGROUND
The increase in power quality related problems are evident with such high visibility incidents as the recent disruptions at the stock exchanges and the air traffic control system in the United States. To those involved with power quality on a daily basis, this comes as no surprise. The increased dependence on computer-based and other electronic equipment with a lower tolerance to various types of power quality phenomena is a large factor.
This increased susceptibility is based on a number of factors, including the lower logic voltage levels, increased clock frequencies, interconnection of equipment through LANs, and escalating percentage of nonLinear Loads. Just as important is the restructuring within industrial/commercial and electric utilities that have dispersed and sometimes eliminated the PQ experts within these organizations. The result is that there are more problems for less experienced people to handle.
There are two different approaches to solving power quality related problems: preventative/predictive maintenance and forensic-type investigations. Due to lack of understanding and increased workloads, the after-the-fact investigations still seem to dominate, though they are clearly the most difficult to solve. Both approaches can use simple rules that will help solve most power quality related problems. While the more complex causes will probably require the knowledge of the experienced person, fortunately, these are the minority of cases.
Before going into the simple rules and procedures, a common set of terms needs to be defined. In North America, the predominate source of these is the IEEE 1159 Recommended Practice on Power Quality Monitoring [1]. In Europe, EN50160 coupled with the UNIPEDE Voltage Characteristic documents are good sources. While both are very useful, the IEEE 1159 currently has a more thorough set of definitions for power quality phenomena, so it will be used here, as defined in Appendix A.
PREVENTIVE MAINTENANCE APPROACH
The preventive maintenance or pro-active approach has been used by many companies to prevent significant financial burdens from lost productivity. Whether it is monitoring the outputs of a UPS while off-line or harmonic levels of a transformer that needs to be derated to prevent shortening its life, this approach is clearly the preferred method. However, it often difficult to get implemented, as many do not see the benefits until after the disaster occurs.
Doing a preventive maintenance monitoring program usually involves the following steps: plan/prepare, inspect, monitor, analyze, and implement a solution. This is often an iterative process, as the first solution may only mitigate part of the problem. One of the more difficult tasks for the less experienced person is the analysis of the data. Numerous papers have been written on the other steps, so the following discussion will focus on the analysis step. The following preventive maintenance program concentrates on steady state conditions, though many rules apply to intermittent conditions as well.
It is assumed that a power quality monitor that can make an accurate survey is used. To do such, the monitor should have the ability to simultaneously capture RMS variations on a cycle-by-cycle basis, transients down to the microsecond level, and harmonic distortion at least to the fourthieth. The measuring voltage inputs should be high-impedance, differential inputs that can be used in both wye and delta circuits without assuming balanced conditions.
Current transformers should have an adequate bandwidth to capture both steady state and transient waveforms. This is often not so when CTs are clamped on the secondary of metering current transformers. Often today, voltage transients are clamped by surge suppression devices, so the way to reliably detect transients is through the triggering and monitoring of current transients.
The monitoring period should last at least one business cycle. A “business cycle” is how long it takes for the facility to repeat the pattern of operation. In industrial locations that run three identical shifts, seven days per week, monitoring may only take eight hours. Most facilities will find that a business cycle is one week. It may be necessary to repeat the survey several times per year due to seasonal changes, such as increases in ESD in the winter months in colder climates. Monitoring should also be done at various places throughout the facility. Typically, the survey begins at the point-of-common- coupling (PCC), which is where the electric utility service meets the building service. Next, monitoring is done at the distribution panels on each floor, followed by outlets at the end of each branch circuit. Data at critical loads in the facility should also be included. While this may seem like a lot of data, having this baseline and profile of the facility will be extremely helpful when future disturbances happen.
Once the data has been collected, it is typically transferred into desktop or laptop computers for analysis using PC software programs. Limits on what is acceptable values can be found in such publications as the FIPS PUB 94 – Guideline on Electrical Power for ADP Installations, shown in Appendix B. Local safety agencies or equipment manufacturer’s specification should be observed, especially if they are more restrictive.
What the effect of being outside these limits would depend on the susceptibility of the equipment, the “stiffness” of the power system, and what other factors are present at the same time. These are not absolute limits, but rather references to raise questions. The neutral-to-ground voltage in a 120V, single phase system, is recommended to be between 0.5 and 3 Vrms. [2] If the voltage is near zero volts, then the presence of an illegal neutral-to-ground bond should be suspected. If the voltage is very high, then the absence of a reliable neutral or ground connection should be looked for.
The presence of voltage modulation (or fluctuation) can result in light flicker, depending on the frequency of the modulation. Based on EN60868, a variation of less than 1% at 9Hz with incandescent lighting can be noticeable.[3] In NEMA MG-1 and IEEE Std 112, they recommend a 10% derating of an electric motor with just a 3% voltage imbalance [4,5]. With proliferation of nonlinear loads, such as PCS and printers, being placed throughout facilities often without regard for maintaining balanced loading, a 3% voltage unbalance is non uncommon.
Analysis of several other parameters is useful. The harmonic distortion for both current and voltage should be reviewed. IEEE 519 Recommended Practice on Harmonics in Power Systems and the IEC 1000-4-7 should be consulted for limits specified for individual harmonic amplitudes and total harmonic distortion value. Is the harmonic distortion severe enough that transformers and other inductive devices need to be derated?
A look at the harmonic spectrum from a FFT or DFT can give clues about what type of equipment is operating on the circuit and is it operating correctly. For example, if there is a high percentage of even harmonics, this would suggest the presence of half-wave rectification. If the equipment on the circuit utilizes such, then that may be an acceptable value. However, if the equipment only has full-wave rectifiers in the power supplies, this may indicate that part of the semiconductor bridge circuit is not operating properly.
The harmonics for multi-pole converters usually show up as harmonic pairs, h=p*n+/-1, where h is the harmonic number, p the number of poles, and n is an integer from one on. For example, a six-pole converter (three phase full wave bridge rectifier) would have harmonics at the 5th and 7th, 11th and 13th, 17th and 19th, and so on.
Two other parameters to look at are the source and load impedance. Source impedance is considered as the equivalent impedance of all of the wiring and transformer impedances (plus any loads) looking back toward the source. The load impedance is defined here as the equivalent impedance of all the loads and circuits looking away from the source.
A reasonable approximation of these values can be derived using the formula’s presented in the IEEE Std 1100, Recommended Practice for the Grounding and Powering of Sensitive Electronic Equipment, also known as the Emerald Book [6]. Based on Ohm’s Law, which states that Voltage = Current * Impedance, Load Impedance equals V line-to-neutral divided by I line-to-neutral. While the value is not an exact value unless signals from the entire frequency spectrum are present, it is useful for determining the effect of loads switching on and off.
Similarly, the source impedance is an approximation derived by taking the difference between two voltages at different times and dividing that value by the difference between two currents at the same time, or (V1-V2)/(I1-I2). This will give a value useful for determining how “stiff” the source is. It can also be used to calculate how severe a sag would result when various loads are turned on. For example, if the source impedance is 1 ohm on a 120Vrms circuit with 10A normal load, switching in a load that has an impedance of 11 ohms will result in a sag down to 100V. Source impedance values more than one ohm should be investigated.
If the power quality analyzer used records harmonic magnitudes and phase angles over time under various loading conditions, then harmonic impedances can also be calculated. This can be helpful in identifying potential resonances with system impedances, such as power factor correction capacitors.
During the preventive maintenance monitoring period, obtaining data is also possible as to the frequency of occurrence of power quality phenomena that are not steady-state conditions, such as sags, swells, transients and interruptions. This data can be either compared directly against the susceptibility specifications if supplied by the equipment manufacturer, or statistically compared against the various survey results that have been published in recent years. How to analyze the cause of the disturbance will be covered in the next section.
In North America, there are three recent studies that are useful in comparing against what is considered “normal”, as far as the frequency of different types of power quality phenomena. The National Power Laboratories (NPL) survey was done at the point-of-utilization, the Canadian Electric Association (CEA) study was done at the point-of-common-coupling, and the Electric Power Research Institute (EPRI) survey was done at the distribution voltage levels. [7] Most European countries have also done such surveys, such as the Enel study in Italy, the East Midlands study in England, and the IQF study in France.
In summary, the preventive maintenance program can identify parameters that are likely to result in long-term system degradation or make the system vulnerable to power quality phenomena, such as low nominal line voltage that can be corrected with a transformer tap change. With many power quality monitors and software available in today’s marketplace, such a program does not require much of the user’s time nor effort.
SUMMARY
Using a power quality monitor to do preventive maintenance surveys and/or after-the-fact investigations requires the knowledge of Ohm’s and Kirchoff’s Laws. The data gathered from the survey is compared against acceptable limits to determine what parameters could be affecting the proper operation of equipment. For the forensic investigation, the direction of the power quality phenomena is determined first (source or load generated). Then, by analyzing the characteristics of the voltage and current waveforms and comparing them against those produced by different types of loads or system operations, the source in many cases can be quickly tracked down.